HOBUT Energimätare 3 avfasad Kalibrerad 85 mm sifferhöjd 105 mm 105 mm

Antal (1 enhet)*

2 404,45 kr

(exkl. moms)

3 005,56 kr

(inkl. moms)

Add to Basket
välj eller skriv kvantitet
I lager
  • Dessutom levereras 2 enhet(er) från den 30 mars 2026
Behöver du mer? Ange den kvantitet du behöver och klicka på "Kontrollera leveransdatum"
Enheter
Per enhet
1 +2 404,45 kr

*vägledande pris

RS-artikelnummer:
914-5357
Tillv. art.nr:
C-TRAN-100A
Tillverkare / varumärke:
HOBUT
Hitta liknande produkter genom att välja ett eller flera attribut.
Välj alla

Varumärke

HOBUT

Serie

C-TRAN

Produkttyp

Energimätare

Utstanshöjd

105mm

Antal faser

3

Utstansbredd

105mm

Sifferhöjd

85mm

Minsta arbetsstemperatur

0°C

Maximal arbetstemperatur

60°C

Djup

59mm

Standarder/godkännanden

BS 4889, BSEN 60688, CE, cUL, EN 61010-1, EN 61326-2, IEC 1036, IEC 359, IEC 60044-1, IEC 688, IEC 801.EN 55020, UL

IsCalibrated

Ja

COO (ursprungsland):
GB

C-TRAN 3 Phase CT with In-built Power Meter


The C-Tran is a combined 3 phase multi function AC power transducer and a 3 phase current transformer in one. The meter is fully programmable through either of the two communication ports. The C-Tran can replace traditional multi function meters and 3 separate current transformers with this all-in-one product with RS485 output.

• RS485 output

• Non-volatile EEPROM memory for storing energy registers, current and voltage ratios and calibrated data

• 2 communication ports

• Accuracy class 0.2 to IEC688

• Multiple installation options

• 3 phase current options; 100A (914-5357), 160A (914-5351) and 250A (914-5360)

Communication Ports


Port 1:

The port has a fixed data format that can also retrieve measurements and set the transducer operating parameters. Only the baud rate and endian format can be changed on this port.

Port 2:

The port is used as the main communication port. It uses Modbus protocol to retrieve measurements and change the transducer operating parameters. It also enables the connection of a host computer, PLC, RTU or Data logger.

Parameters measured:


• Phase Voltage (V)

• Line Voltage (V)

• Phase Current (I)

• Frequency (Hz)

• Active Power Per Phase (W)

• System Active Power (W)

• Reactive Power Per Phase (VAr)

• System Reactive Power (VAr)

• Apparent Power Per Phase (VA)

• System Apparent Power (VA)

• Import Active Power (W.h)

• Import Reactive Power (VAr.h)

• Apparent Energy (VA.h)

• System Power Factor (P.F.)

• Amp Demand (Ad)

• Maximum Amp Demand (Max.Ad)

• Import Watt Demand (Wd)

• Maximum Watt Demand Import (Max.Wd)

• VA Demand (VAd)

• Maximum VA Demand (Max. VAd)

• Neutral Current

• Hours Run—Voltage based

Relaterade länkar