Megger LRCD220-FR Loop Impedance & RCD Combined Tester, Loop Impedance Test Type 2 Wire 500V, RCD Test Type AC
- RS-artikelnummer:
- 537-7923
- Tillv. art.nr:
- LRCD220-FR
- Tillverkare / varumärke:
- Megger
I lager för avsändande samma dag
Nästa dag-leverans inte möjlig
Lagt till varukorgen
Pris (ex. moms) Varje
11 398,82 kr
(exkl. moms)
14 248,52 kr
(inkl. moms)
Enheter | Per unit |
1 + | 11 398,82 kr |
- RS-artikelnummer:
- 537-7923
- Tillv. art.nr:
- LRCD220-FR
- Tillverkare / varumärke:
- Megger
Lagstiftning och ursprungsland
RoHS-status: Inte relevant
- COO (Country of Origin):
- GB
Produktdetaljer
Megger Loop Impedance and RCD Combined Tester, 10mA to 1000mA RCD Test Current Range, Armoured Rubber Case - LRCD200 Series - LRCD220-FR
Make sure your electrical safety systems are in top-notch condition with this loop impedance and RCD combined tester from Megger. Its no-trip feature means you can check all devices over 30mA without accidental activation. The handy instrument can also read the trip time of your RCD to ensure it reacts quickly to fault currents, with an auto-test function letting you focus on the breaker during the process. For additional peace of mind, you can perform 2-wire fast testing, phase-to-phase and phase-to-earth measurements on this versatile device.
Features & Benefits
• RCD test current range of 10mA to 1000mA gives you a broad scope
• IP54 rating demonstrates protection against water sprays for a weatherproof unit
• Integrated voltmeter lets you read voltage levels
• Backlit display for convenient viewing in low-light settings
• IP54 rating demonstrates protection against water sprays for a weatherproof unit
• Integrated voltmeter lets you read voltage levels
• Backlit display for convenient viewing in low-light settings
Applications
• Electrical engineering
• Security systems
• Control panels
• Lighting fixtures
• Security systems
• Control panels
• Lighting fixtures
How does earth loop impedance testing work?
Testers like this one measure the impedance of the electrical loop by releasing a test current to the circuit. This tells you if the system can deliver enough current to activate the fuse in case of electrical faults and disconnect quickly enough to prevent a fire outbreak.
Specifikationer
Attribute | Value |
---|---|
Loop Impedance Test Type | 2 Wire |
Test Equipment Type | Combined Loop & RCD Tester |
Maximum Voltage Measurement | 500V |
RCD Test Type | AC Selective, DC Selective |
PSC Display | Yes |
Best Loop Test Accuracy | ±2% |
RCD Test Current | 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000mA |
Non-Trip Loop Test | Yes |
Safety Category | CAT III 300 V, IEC 61010 |
Display Type | LCD |
Battery Life | 2000 Tests |
Battery Type | AA |
Power Source | Battery |
Dimensions | 203 x 148 x 78mm |
Weight | 980g |
Width | 148mm |
Length | 203mm |
Plug Type | BS 1363 |
Maximum Operating Temperature | +40°C |
Safety Category Level | CAT III |
Safety Category Voltage | 300V |
Minimum Operating Temperature | -5°C |
Height | 203mm |
Model Number p | LRCD220 |