Better World
Schneider Electric LR2K Thermal Overload Relay 1NO + 1NC, 2.6 → 3.7 A F.L.C, 3.7 A Contact Rating, 100 W, 250 V
- RS-artikelnummer:
- 758-967
- Tillv. art.nr:
- LR2K0310
- Tillverkare / varumärke:
- Schneider Electric
40 I lager för avsändande samma dag
25 Inom 1 arbetsdag(ar) (UK lager)
Lagt till varukorgen
Pris (ex. moms) Varje
710,01 kr
(exkl. moms)
887,51 kr
(inkl. moms)
Enheter | Per unit |
1 + | 710,01 kr |
Better World
Vårt Better World-sortiment innehåller produkter som gör det enkelt för dig att göra ett grönare produktval som du kan lita på. Klicka här för mer information.
- RS-artikelnummer:
- 758-967
- Tillv. art.nr:
- LR2K0310
- Tillverkare / varumärke:
- Schneider Electric
Lagstiftning och ursprungsland
RoHS-status: Inte relevant
- COO (Country of Origin):
- CZ
Produktdetaljer
Schneider Electric Mini Thermal Overload Relays - LR2-K Range
Schneider Electrics K thermal overload relays are adjustable from 0.11 to 11.5 A, they have been predominantly designed for use in applications that require motor protection.
This range of mini thermal overload relays feature compensated and phase failure sensitivity, the range also offers manual and automatic reset. Each overload relay has 3-poles and screw clamp terminals.
This range of mini thermal overload relays feature compensated and phase failure sensitivity, the range also offers manual and automatic reset. Each overload relay has 3-poles and screw clamp terminals.
Features & Benefits
Commonly referred to by the range short name - LR2K
Easy maintenance checks, check the tightening of cables through conducting thermographic testing and checking the mechanical operation of the product through manually operating the test, reset and stop buttons
Direct mounting under a contactor is achievable
Standards - IEC 947, BS4941, VDE 0660, NFC63-650
Standards - CSA, UL, DEMKO, NEMKO, SEMKO, FIMKO, PTB
Easy maintenance checks, check the tightening of cables through conducting thermographic testing and checking the mechanical operation of the product through manually operating the test, reset and stop buttons
Direct mounting under a contactor is achievable
Standards - IEC 947, BS4941, VDE 0660, NFC63-650
Standards - CSA, UL, DEMKO, NEMKO, SEMKO, FIMKO, PTB
Applications of a Contactor and Control Overload Relay
The majority of the time is to protect a motor
To detect both overload conditions and fault conditions to then announce trip command for a protective device
To deactivate a device whenever it pulls high current
Sometimes developed into microprocessor systems and solid-state electronics
To detect both overload conditions and fault conditions to then announce trip command for a protective device
To deactivate a device whenever it pulls high current
Sometimes developed into microprocessor systems and solid-state electronics
Schneider Electric TeSys K LR2K0310 Differential Thermal Overload Relay.
- Application – Motor protection
- Compatible with LC7k, LP1K, LP4K, LC1K.
- DC and AC Network.
- Class 10A.
- Thermal protection adjustment 2.6 to 3.7 A.
- Contacts 1 NO and 1 NC.
- Phase failure sensitivity to IEC 60947-4-1.
- Yellow trip indicator.
- Screw clamp terminals.
- Height 58 mm.
- Width 45 mm.
- Depth 65 mm.
- Net weight 0.145 kg.
Standards.
- IEC 60947 / VDE 0660, BS 4941, NF C 63-650.
- IP2x to IEC 60529.
- Fire resistance 850° to IEC 60695-2-1.
- Shock resistance NO contact 10 Gn for 11 ms – to IEC 60068-2-27.
- Shock resistance NC contact 10 Gn for 11 ms – to IEC 60068-2-27.
- Vibration NO contact 2 Gn, 5 to 300 Hz to IEC 60068-2-6.
- Vibration NC contact 2 Gn, 5 to 300 Hz to IEC 60068-2-6.
Specifikationer
Attribute | Value |
---|---|
FLC Motor Rating | 2.6 → 3.7 A |
Contact Current Rating | 3.7 A |
Range | TeSys |
Pole Configuration | 3P |
Series | LR2K |
Mounting Style | Direct Contactor |
Power Rating | 100 W |
Normal State Configuration | 1NO + 1NC |
Terminal Type | Screw |
Reset Method | Automatic, Manual |
Number Of Auxiliary Contacts | 2 |
Width | 45mm |
Depth | 65mm |
Length | 116mm |
Maximum Operating Temperature | +55°C |
Minimum Operating Temperature | -20°C |
Better World Verification | Green Premium |
Better World Product | Yes |
Operating Temperature Range | -20 → +55 °C |
Contact Voltage Rating | 690 V ac |
Control Voltage | 250 V dc, 690 V ac |