- RS-artikelnummer:
- 183-2844
- Tillv. art.nr:
- FK1610
- Tillverkare / varumärke:
- HENSEL
Tillfälligt slut i lager – restorder för leverans 2024-05-21
Lagt till varukorgen
Pris (ex. moms) Varje
2 409,30 kr
(exkl. moms)
3 011,62 kr
(inkl. moms)
Enheter | Per unit |
1 + | 2 409,30 kr |
- RS-artikelnummer:
- 183-2844
- Tillv. art.nr:
- FK1610
- Tillverkare / varumärke:
- HENSEL
Datablad
Lagstiftning och ursprungsland
- COO (Country of Origin):
- DE
Produktdetaljer
Cable junction box 1.5-2.5 mm², Cu
Connection box 1.5-10 mm², Cu
5-pole per pole 8 x 1.5 mm² r, 4 x 2.5 mm² r, 2 x 4 mm² r, 2 x 6 mm² r, 2 x 10 mm² sol (remove wire protection)
connecting terminal made from ceramic with resistance to high temperatures
Included cable entry: 3 EDKF 32,
sealing range: 8-23 mm, IP 65
IP 66 using AKMF cable glands, please order separately
Intrinsic fire resistance in accordance with DIN 4102-12 (German standard) in combination with function-retaining cables
Tested with the cable manufacturers Dätwyler and Eupen for the intrinsic fire resistance E30 up to E90, see test certificate no.: P-MPA-E-15-018 valid till 9 May 2026, download available from www.hensel-electric.de > type - documents
Tested for insulation integrity PH120 in accordance with BS EN 50200 in connection with insulation retaining cables, see test certificate, download available from www.hensel-electric.de > type - documents
Screw anchors enclosed can be used for concrete C20/25, limestone blocks KSV 12, building bricks MZ 12 and clinker bricks KS 12
For normal environment and protected outdoor
Colour: orange, RAL 2003
Connection box 1.5-10 mm², Cu
5-pole per pole 8 x 1.5 mm² r, 4 x 2.5 mm² r, 2 x 4 mm² r, 2 x 6 mm² r, 2 x 10 mm² sol (remove wire protection)
connecting terminal made from ceramic with resistance to high temperatures
Included cable entry: 3 EDKF 32,
sealing range: 8-23 mm, IP 65
IP 66 using AKMF cable glands, please order separately
Intrinsic fire resistance in accordance with DIN 4102-12 (German standard) in combination with function-retaining cables
Tested with the cable manufacturers Dätwyler and Eupen for the intrinsic fire resistance E30 up to E90, see test certificate no.: P-MPA-E-15-018 valid till 9 May 2026, download available from www.hensel-electric.de > type - documents
Tested for insulation integrity PH120 in accordance with BS EN 50200 in connection with insulation retaining cables, see test certificate, download available from www.hensel-electric.de > type - documents
Screw anchors enclosed can be used for concrete C20/25, limestone blocks KSV 12, building bricks MZ 12 and clinker bricks KS 12
For normal environment and protected outdoor
Colour: orange, RAL 2003
Specifikationer
Attribute | Value |
---|---|
Dimensions L x W x H | 155 x 92 x 210mm |
Material | Polycarbonate |
Length | 155mm |
Width | 92mm |
Height | 210mm |
IP Rating | IP65, IP66 |
Number of Terminals | 5 |
Colour | Orange |
Number of Ways | 3 |
Current Rating | 57A |