Broyce Control Level Controller -, 230 V ac 1


8 I lager för leverans inom 1 arbetsdagar
Add to Basket

Pris (ex. moms) Each

599,00 kr

(exkl. moms)

748,75 kr

(inkl. moms)

Enheter

Lagt till varukorgen

RS-artikelnummer:
361-1603
Tillv. art.nr:
B8LCR 230VAC
Tillverkare / varumärke:
Broyce Control
COO (Country of Origin):
GB
EnheterPer unit
1 +599,00 kr

Liquid Level Controller, Plug In Base


Controls maximum and/or minimum levels of conductive liquids
’Pump-up’ or ’Pump-down’ modes selectable via switch
Adjustable sensitivity, 5 to 100kΩ
One or two probe operation
Low voltage, ac current across probes prevents electrolysis phenomena
Ambient temperature; -20 to + 60°C
Dimensions; H89mm x W40mm, x D92mm


Note

1. If using metal tank, connect “pin 1” and earth to the tank
2. If supply is interrupted for ≤0.5s in “pump-up” mode, the relay will energise immediately.
In “pump-down” mode relay remains de-energised
3. For single probe operation, link terminals “pin 1” and “pin 7”

Approvals

UL recognised component for Canada and US

Liquid Level Relays are used to monitor the levels of conductive liquids, and are available in Up/Down, Minimum, Maximum, and Fill/Empty variations. Liquid Level Relays are straightforward to install and safe to use.

Application Examples

Liquid Level Relays (Conductive Level Sensors) are used in a wide variety of applications including waste water management and the monitoring and management of corrosive liquid media, and designed specifically to provide for the:

Monitoring and control of liquid levels
Protection of pumps against dry running
Ability to detect liquid leaks in a system
Control of media mixing ratios
Control of liquid levels

AttributeValue
Number of Inputs1
Probe Voltage17V ac
Supply Voltage230 V ac
Overall Length92mm
Overall Width40mm
Overall Depth80mm
Minimum Operating Temperature-20°C
Maximum Operating Temperature+60°C