Gossen Metrawatt M503A Electrical Tester

Datablad
Lagstiftning och ursprungsland
RoHS-Försäkran
COO (Country of Origin): SK
Produktdetaljer

Starter package PROFITEST INTRO M503A

Starter package PROFiTEST INTRO, consisting of PROFiTEST INTRO M520T, PRO-Schuko-Measuring-Adapter Z503K, PRO-Jumper Z503J, Universal Carrying Pouch F2010 Z700G, Battery Pack Master Z502H and charger Z502R.

PROFITEST INTRO M520T Tester, IEC 60364-6 / DIN VDE 0100-600

Measurement of RLO, ZL-PE, ZL-N, RINS, RE, ΔU, phase
sequence and voltage
OFFSET Management RL-PE / RN-PE / RL-N
Measuring functions can be selected directly via the rotary switch
Testing of RCD types A, AC, F, B, B+, EV, MI and G/R, as well as SRCDs and PRCDs
Display of approved fuse types for electrical systems
Phase sequence measurement (including highest line-to-line voltage)
Measuring of contact voltage by Finger contact
Connection of an RFID reader or a barcode scanner
Individual measured value memory and memory structure setup
Help functions with wiring diagrams
Bidirectional data exchange via USB, DDS-CAD and epINSTROM
Measuring category: CAT III 600 V / CAT IV 300 V
International prompting (12 languages)
ETC software (Electrical Testing Center) for, amongst other functions, creating tree structures and documentation per ZVEH

Note

Comprehensive operating instructions available on the Internet for download at www.gossenmetrawatt.com

Specifikationer
Attribute Value
Loop Impedance Test Type Phase to Earth, Phase to Neutral
RCD Ramp Test Yes
Insulation Test Voltage 3700V
Maximum Voltage Measurement 600V
Test Type Wiring Polarity
Earth Resistance Measurement Yes
Continuity Test Current 15mA
RCD Test Type DC Selective
Remote Switch Mode Yes
Test Standards DIN VDE 0100-600, IEC 60364-6
IP Rating IP40, IP52
Minimum Continuity Resistance 300mΩ
Dimensions 130 x 225 x 140mm
Length 130mm
Width 225mm
Safety Category Voltage 300 V, 600 V
Power Source Battery, Mains
Maximum Continuity Resistance 9.99kΩ
Plug Type Type F - Schuko plug
Safety Category Level CAT III, CAT IV
Weight 1.5kg
Model Number p M503A
Height 140mm
Minimum Operating Temperature 0°C
Maximum Operating Temperature +40°C
Display Type LCD
Safety Category CAT III 600 V, CAT IV 300 V
Battery Type AA
I lager för leverans inom 2 arbetsdagar
Pris (ex. moms) Each
13 597,10 kr
(exkl. moms)
16 996,38 kr
(inkl. moms)
Enheter
Per unit
1 +
13 597,10 kr
Nästa dag-leverans inte möjlig
Related Products
Test box designed to provide confirmation that electrical ...
Description:
Test box designed to provide confirmation that electrical installation testers continue to operate properly, and maintain their accuracy and consistency between calibrations. Tests the full range of a testers capability.Does not trip RCD protected circuits.Tests to regulations BS7671, BS EN61557 ...
An in-line holder to connect individual components with ...
Description:
An in-line holder to connect individual components with 4mm safety test leads. Holder comprises 2x4mm safety plugs and 2x4mm safety sockets rated at 600V (CAT II)Component solder connections are provided within the screw-together adaptor casing Components clearly visible through transparent ...
Support Accessories:. Multifunction installation testers to verify the ...
Description:
Support Accessories:. Multifunction installation testers to verify the safety of electrical installations in industrial, commercial and domestic applicationsMeet the requirements of IEC 60364, HD 384 and BS 7671 17th Edition wiring regulationsLarge illuminated display with exceptionally wide viewing angleRugged: ...
Ø 4 mm safety component holder for experimental ...
Description:
Ø 4 mm safety component holder for experimental circuit board SET4.Component mounting: welded onto terminals supplied.Protection level: IP2X.Available in two-pole or four-pole versions.For use in education, research and development etc.